Supply range of 25kW Three Phase Diesel Generator:
Specification of Three Phase Diesel Generator:
Model | A-QC34 | |
Max. Power | kVA | 34 |
kW | 28 | |
Rate Power | kVA | 31 |
kW | 25 | |
Frequency | Hz | 50 |
Rate Voltage | V | 400/230 |
Rate Current | A | 45.1 |
Dimension For Open-type Genset | mm | 1450 X 750 X 1050 |
Weight For Open-type Genset | kg | 640 |
Dimension For Soundproof Genset | mm | 1800 X 850 X 1200 |
Weight For Soundproof Generator | kg | 950 |
Noise Level at 7 Meters | dBA | 70 |
Fuel Tank Capacity | Litres | 100 |
Battery | One of 80A Free Maintenance Battery |
Specification of Diesel Engine:
Engine Manufacturer | Anhui Quanchai Engine Co., Ltd. | |
Engine Brand | Quanchai | |
Engine Model | QC4102D | |
No. of Cylinder | 4 Cylinder in line | |
Aspiration | Naturally Aspirated | |
Governor | Mechanical | |
Engine Max. Output Power | kW | 33 |
Displacement | L | 3.857 |
Starting Voltage | V | 12 |
Bore | mm | 102 |
Stroke | mm | 118 |
Lubrication Oil Capacity | L | 7 |
Compression Ratio | 18 : 1 | |
Intake Air Flow | M3/Min | 2.5 |
Fuel Consumption at 100% Load | L | 9.6 |
Specification of Brushless Alternator:
Alternator Manufacturer | Fuzhou Hosem Power Co., Ltd. | |
Alternator Model | ASF184G | |
Alternator Brand | Hosem | |
Rate Output | kVA | 31 |
Frequency | Hz | 50Hz |
Altitude | M | ≤1000 |
Insulation | Class H | |
Voltage Regulation | SX460 | |
Protection Grade | IP23 | |
Working Temperature without Output Decrease | ≤40℃ | |
Phase | 3 Phase | |
Temperature Rise | 125 Degree Celsius | |
Alternator for optional | Leroy Somer, Marathon, Mecc Alte and Hosem Brushless alternator for optional | |
Specification of Automatic Control Panel:
Controller Brand | ComAp Made in Czech | |
Controller Model | AMF9 | |
Breaker Brand | Delixi | |
Breaker Capacity (A) | 63 | |
Battery Charger | Smartgen Model BAC06A | |
Emergency Stop Button | Supply | |
Automatic Mains Fail (AMF) | Supply | |
Fuel Level | Supply | |
Automatic Transfer Switch | ATS as optional part | |
Mains Monitor | Supply with AMF Function | |
The control panel supply the full protection with alarm and shutdown of the diesel generator include Start-up fault (generator set shutdown), High coolant temperature (alarm and generator set shutdown), Low oil pressure (alarm and generator set shutdown), Low fuel level (alarm), Low cooling fluid level alarm (as optional), Overload (alarm and generator set shutdown), Battery voltage high (alarm). | ||
Optional controller: Each model of Deepsea, Smartgen, ComAp brand controller. |
FAQ:
Q: Are you trading company or manufacturer?
A: We are factory.
Q: What is your power range of your diesel generator?
A: we can provide power from 3kVA-3000KVA
Q: How long is your delivery time?
A: The delivery time is about 20days after we get the deposit or L/C.
Q: What is your terms of payment?
A: T/T 30% in advance for deposit and T/T 70% balance paid before shipment or 100% LC at sight.
Q: What is your warranty period?
A: Our payment terms is one year or 1000 working hours, subject to which comes first. But based on some special project, we can extended our warranty period.
Q: Do you offer OEM service?
A: Yes