Specification of Ricardo Diesel Generator and Datasheet of R4105BZLDS Engine
Model | A-KF83 | |
Standby Power | kVA | 83 |
kW | 66 | |
Prime Power | kVA | 75 |
kW | 60 | |
Frequency | Hz | 50 |
Output Voltage | V | 400/230 |
Oil Consumption | L/H | 0.053 |
Dimension For Open-type | mm | 1650 X 800 X 1350 |
Weight For Open-type | kg | 950 |
Dimension For Soundproof | mm | 2900 X 1080 X 1500 |
Weight For Soundprof | kg | 1550 |
Noise For Soundproof | dBA | 75 |
Engine Manufacturer | Shandong Kofo Power Co. Ltd. | |
Engine Brand | Kofo | |
Engine Model | R4105BZLDS | |
No.of Cylinder | 4 Cylinder in line | |
Bore | mm | 105 |
Stroke | mm | 125 |
Displacement | L | 3.76 |
Aspiration | Turbocharger and After-cooled | |
Rate Speed | R.P.M. | 1500 |
Governor | Mechanical | |
Lubrication Oil Capacity | L | 15 |
Starting Voltage | V | 12 |
Engine Max.Output Power | kW | 82 |
Ricardo Generator in Assemble
Standard Compose of 60kW Ricardo Diesel Generator
Original Ricardo Engine
Air Cleaner(Dry-cartridge type)
Fuel Pump
Fuel Filter
Thermostat and Housing
Dry Exhaust Manifold
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor
Housing & Flywheel
Charging Alternator
Battery Rack & Cables
First filling of oil and filters
First filling of coolant
Brushless Alternator
Self-ventilated and drip-proof construction
Synchronous, Brush-less, Self Exciting, Self Regulating
Direct Coupled With Flex Disk
12 Leads winding
Class H Insulation
Drip-Proof Construction
Exhaust
Built-in Industrial Muffler for Open generators
Built-in Residential Muffler for Silent generators
Rain Cap
Handling
Fork lift facilities
Lifting and holding down points
Base Frame
Heavy duty quality steel fabricated welded base plate
Heavy duty anti-vibration mountings
Stub-up area
Electrical System
Battery (for 50HZ is supplied as standard)
Battery rack and cables
Engine driven battery charger
Battery disconnect switch
32A/4P CHINT MCCB
Canopy(for silent units)
Heavy duty lockable handles in each door
Large doors for easy access for service and monitoring
Coolant refilling specific hatch
Sound foam
Modular bolted assembly after painting.
Powder coating paint for outdoor usage.
Weatherproof sealed joints.
Cut using high precision numeric control technology.
Bent using high precision numeric control technology.
Glazed acoustic sealed control panel door.
Fuel filter outside enclosure.
In base oil and coolant drains.
Control Panel
HT2000 Control System
Automatic Start Control Panel
* Compact gen-set controller for gensets operating for automatic start/stop, data measure and alarming.
* Battery Charger(to be supplied by mains into the 208-240V range)
* On/Off button
* Emergency stop buttion
Packing
EVA Foam Plastic wrap protection package
Alternator, Engine and Generating set operator's manual are supplied together with electrical drawings.