Specification:
Model | A-P186H | |
Standby Power | kVA | 186 |
kW | 149 | |
Prime Power | kVA | 169 |
kW | 135 | |
Frequency | Hz | 60 |
Output Voltage | V | 240 |
Oil Consumption | L/H | 0.42 |
Dimension For Open-type | mm | 2235 X 730 X 1595 |
Weight For Open-type | kg | 1090 |
Dimension For Soundproof | mm | 2480 X 1100 X 1830 |
Weight For Soundprof | kg | 1790 |
Engine Model | 1106D-E70TAG2 | |
No.of Cylinder | 6 Cylinder in line | |
Bore | mm | 105 |
Stroke | mm | 135 |
Displacement | L | 7.01 |
Cooling Fan Air Flow | m3/min | 174 |
Compress Air Flow | m3/min | 9.4 |
Exhaust Gas Flow | m3/min | 24.4 |
Exhaust Gas Temperature | ℃ | 478 |
Lubrication Oil Capacity | L | 16.5 |
Cooling Water Capacity | L | 21 |
Starting Voltage | V | 12 |
Engine Max.Output Power | kW | 176 |
Alternator Model | UCI 274 E | |
Alternator Brand | Stamford | |
Rate Output | kVA | 178 |
Frequency | Hz | 60 |
Altitude | M | ≤1000 |
Insulation | Class H | |
Protection Grade | IP23 | |
Alternator for choice | We also have Leroy Somer, Marathon, Mecc Alte and Chinese brand Brushless alternator for your choice. | |
Control Panel Model | AF500 | |
Controller | Deepsea Brand Model DSE7320 | |
Function of control panel | Automatic genset start/stop | |
Automatic battery charger | ||
Emergency stop | ||
AMF (Automatic Mains Fault) | ||
Remote control | ||
Micro-processor based design | ||
LED alarm indication and Sound alarm | ||
Display of the controller | Generator voltage: Uab, Ubc, Uca | |
Generator current: Ua, Ub, Uc | ||
Generator temp.: ℃/℉ both display | ||
Generator frequency: Hz | ||
Generator power: kW, kVA, kWh, kVAr, kVArh, kVAh | ||
Generator starts count: 999999 times (Max) | ||
Generator pressure: kPa/Psi/Bar both display | ||
Charging Voltage: V | ||
Battery Voltage: V DC | ||
Protection of Diesel Generator | Over / Under Speed Alarm and Shutdown | |
Start / Stop Failure Alarm | ||
Over Current Alarm and Shutdown | ||
Under / Over Generator Voltage Alarm and Shutdown | ||
Low Oil Pressure Alarm and Shutdown | ||
High Engine Temperature Alarm and Shutdown | ||
Over Load Alarm and Shutdown | ||
Low and High Battery Voltage Alarm | ||
Lose of Speed Signal Alarm and Shutdown | ||
Charge Fail Alarm |
Our advantages :
1.Inspection
1. Each engine shall be tested at manufacturer’s workshop to certify the engine output according to present standard and fuel consumption in accordance with the site operating condition specified by purchaser on the specification datasheet.
2. All relevant information drawings pertinent to the testing and test procedure shall be transmitted to the purchaser in advance of the test date notification.
3. All accompanied documents are corresponding to the actual situation of generators, including the Qualified Certificate, Parameters and the Performance Index.
2.Guarantee
1) Guarantee Period: One year or 1000 running hours whichever comes first.
2) During the guarantee period, the spare-parts will be sent through your shipping agency in China.
3) Spare-parts can also be sent by air express.
4) 24 hours service hotline is available for customers.
Our Service :
1. If you are interested in our products we sincerely invite you to take a visit of our factory when you are in China. We can drive to pick you up and visit our factory.
2. Suggest the best choice or referential suggestion based on customers’ information. Answer all questions about the product from customer.
3. Build customers’ profiles, follow-up service, make regular calls on customers.
Q1: Any advantages about your company?
-- Fast delivery time
-- Good design and high quality
-- Good service after sale
-- High quality with good price help you get more benefit and beat your competitors
Q2: Can you supply OEM service?
Yes, we can offer OEM service
Q3: How about the service after sale?
We have agents spread all over the world, our service network spanning more than 50 countries so we can ensure fast and good service for our clients. We are recruiting agents, welcome you to be our friend and get a win-win cooperation.