1. SPECIFICATIONS OF GEN-SET | |
Set Model | A-YD30S |
Prime at 50HZ, 40℃ ambient | 24KW 30kVA |
Standby at 50HZ, 40℃ ambient | 26KW 33kVA |
Rated Gen-set output | 230/400V 50Hz |
Rated Relative humidity | ≤ 60 % |
Dimension (L×W×H) | 1760×650×1050mm |
Weight | 580kg |
Fuel consumption 100% prime load | ≤238g/kWh |
Structure of Gen-set |
The Gen-set adopt integrative structure, engine is fix on high strength steel basic frame, anti vibration instrument between the engine and basic frame, cooling fan have protecting cap, control cabinet and circuit breaker installed on Gen-set |
Control system (Optional) |
Basic control panel or Advanced control panel with automatically start-up function and other function |
2. SPECIFICATIONS OF ENGINE | |
Engine Brand | YANG DONG |
Engine Model | Y4102 |
Governor/Class | Mechanical |
Cylinder NO. | 4 |
Engine build | Line |
Start-up method | 24V,electric |
Battery capacity | 70~100A/hr |
Fuel spray pattern | Direct spray |
Aspiration | Natural |
Cooling mode |
Radiator cooled (enclose water) |
Bore and stroke | 102 × 118mm |
Compression ratio | 18.8:1 |
Displacement | 3.857L |
Engine Prime Power at 1500rpm | 32kWm |
Engine Standby Power at 1500rpm | 35kWm |
Fuel type |
Diesel (Natural temperature) |
Filter system |
Adopt whole changeable lubricating oil, fuel filter and air filter |
Exhaust system |
Adopt industrial high efficiency muffler and ripple pump |
Engine derating – altitude |
Above the sea level 1525m high, a fall of 4% from a rise of 300m. |
Engine derating – temperature |
Above the ambient temperature 40℃ high, a fall of 2% from a rise of 11%. |
3. SPECIFICATIONS OF ALTERNATOR | |
Alternator Model | Stamford/PI 144G |
Alternator Type | A.C. Synchronous |
Rated Voltage | 230/400V |
Rated Frequency | 50HZ |
Rated speed | 1500 RPM |
Voltage regulation mode | Auto |
Alternator voltage regulation | ±0.5% |
Exciting mode | Brushless self exciting |
Power factor | 0.8 (lagging) |
Phase & wires | 3 phase 12 wires |
Rated current | 45.1A |
Efficiency | 86.20% |
Insulation class | H |
Protection class | IP23 |
Single load step to NFPA110 | 100% |
Standards | IEC34-1,NEMA1 |
Ambient Temperature | 40℃ |
Relative humidity | - 15℃ |
Altitude | 1000m |
Weight | 172㎏ |
Applications:
1. Industrial area: real estate, hospital, hotel, bank, construction, factory, oil field, airport, mining, railway
2. Home use: personal use for house, camping, party, etc
3. Telecom, Mobile tower, etc
4. Island, Desert or any place without electricity
5. As for emergency equipment special for natural disasters, such as typhoon, earthquake, heavy snow
6. Standby power or main power, indoor or outdoor using.
Product features:
Good sound insulation effect, 70dBA at 7 meters.
Side doors are mounted on both sides, convenient for daily check and maintenance.
External oil filter design can ensure fuel safety when generating sets outside.
Cabinet and base frame are made of high-quality slabs and coated with excellent coating material, with three layers of bottom-medium-top spraying process and high anti-corrosion and antirust capacity.
Why Choose Hosem Power Generator?
Reasons1: We are More Professional
Most members of Hosem Power have more than 10 years of experience in the generator area, Our mechanical engineers, electrical engineers have more than 20 years of experience in the generator ara. We are always ready to serve to your needs.
Reasons2: Outstanding Quality
Our advantage lies in:
1. Good shock absorption performance: Optimal design of shock absorption system based on computer dynamic simulation.
2. Advanced control system: Full monitoring system control strategy found on reliability design.
3. Low noise: Tailor custom-engineered exhaust silencer system for each set.
4. Green environmental protection: Diesel generator set combined energy-saving and low emission in one.
Reasons3: Strictly QC Before EX-Factory.
Each and every unit is strictly factory tested before shipment.
1) Parts faults testing
2) Fuel tank pressure testing
3) Bolt tightening torque testing
4) Painting thickness testing
5) Voltage bearing and insulation testing
6) Noise testing
7) Loading Testing: 25%, 50%, 75%, 100%, 110% load to check verify that all control systems, alarm and shut-down protection.