Supply Range of 100kVA Volvo Diesel Generator:
Standard Configuration of Volvo Diesel Generator | Optional Configuration for the Volvo Diesel Generator |
1. Volvo Diesel Engine TAD531GE | 1. Soundproof Canopy |
2. Stamford Alternator UCI 274 C | 2. Heavy-duty air filter |
3. Deepsea DSE7320 Controller | 3. Engine Oil Heater |
4. Cooling system with large size radiator and expansion tank | 4. Engine coolant heater |
5. Heavy- duty chassis | 5. Coolant level sensor and alarm |
6. Built-in insulation and anti-vibration dampers | 6. Alternator Anti-condensation heater |
7. Free-maintenance battery | 7. PMG alternator |
8. Charge alternator for diesel engine | 8. Power sockets panel |
9. A.C. 220V battery charger | 9. Daily fuel fank |
10. Cable and bracket for battery | 10. External fuel connections |
11. Battery isolation switch | 11. Automatic fuel refilling device |
12. Circuit breaker | 12. Residential type silencer |
13. Fuel & Water separator | 13. Skid with forklift slots |
14. Oil sump pump | 14. Parallel Panel |
15. Full safety operation protection | 15. ATS (Automatic Transfer Switch) |
16. Emergency stop button | 16. Mobile trailer chassis |
17. Automatic start control system | 17. 4 Pole circuit breaker |
Technical Data of 100kVA Volvo Diesel Generator:
Model | A-V110S | |
Max. Power | kVA | 110 |
kW | 88 | |
Rate Power | kVA | 100 |
kW | 80 | |
Frequency | Hz | 50 |
Rate Voltage | V | 400/230 |
Rate Current | A | 144.3 |
Fuel Tank Capacity | L | 125 |
Dimension For Open-type Genset | mm | 2100 X 850 X 1550 |
Weight For Open-type Genset | kg | 1200 |
Dimension For Soundproof Genset | mm | 2900 X 1080 X 1500 |
Weight For Soundproof Generator | kg | 1780 |
Noise Level for Soundproof Generator at 7M | dBA | 75 |
Battery | Two of 100A Free Maintenance Battery |
Technical Data of Volvo Diesel Engine TAD531GE:
Engine Manufacturer | Volvo Penta Industrial | |
Engine Brand | Volvo | |
Engine Model | TAD531GE | |
No. of Cylinder | 4 Cylinder in line | |
Aspiration | Turbocharged | |
Governor | MECH | |
Engine Max. Output Power | kW | 98 |
Displacement | L | 4.8 |
Compression Ratio | 18 : 1 | |
Starting Voltage | V | 12 |
Bore | mm | 108 |
Stroke | mm | 130 |
Lubrication Oil Capacity | L | 13 |
Intake Air Flow | M3/Min | 6.1 |
Fuel Consumption at 100% Load | L/H | 25.9 |
Technical Data of Stamford Alternator:
Alternator Manufacturer | Cummins Generator Technologies | |
Alternator Model | UCI 274 C | |
Alternator Brand | Stamford | |
Rate Output | kVA | 100 |
Frequency | Hz | 50Hz |
Altitude | M | ≤1000 |
Insulation | Class H | |
Phase | 3 Phase | |
Working Temperature without power decrease | ≤40℃ | |
Working Altitude without power decrease | ≤1000m | |
Automatic Voltage Regulation | SX440 | |
Protection Grade | IP23 | |
Alternator for optional | Leroy Somer, Marathon, Mecc Alte and Hosem Brushless alternator for optional | |
Technical Data of Control Panel:
Controller Brand | Deepsea | |
Controller Model | DSE7320 | |
Breaker Brand | Delixi | |
Breaker Capacity (A) | 160 | |
Battery Charger | Smartgen Model BAC06A | |
Emergency Stop Button | Supply | |
Automatic Mains Fail (AMF) | Supply | |
Fuel Level | Supply | |
Automatic Transfer Switch | ATS as optional part | |
The control panel supply the full protection with alarm and shutdown of the diesel generator include Start-up fault (generator set shutdown), High coolant temperature (alarm and generator set shutdown), Low oil pressure (alarm and generator set shutdown), Low fuel level (alarm), Low cooling fluid level alarm (as optional), Overload (alarm and generator set shutdown), Battery voltage high (alarm). | ||
Optional controller: Each model of Deepsea, Smartgen, ComAp brand controller. |