Generator Set Specification | ||
Max. Power | kVA | 28kVA-280kVA |
kW | 22kW-220kW | |
Rate Power | kVA | 25kVA-250kVA |
kW | 20kW-200kW | |
Frequency | Hz | 400 |
Rate Voltage | V | 115/200V |
Rate Current | A | - |
Fuel Tank Capacity | 8 hours | |
Noise Level for Soundproof Generator at 7M | dBA | 70 |
Battery | Two of 80Amps Free Maintenance Battery |
- Voltage Adjust Ratio: 1% from no load to full load;
- Voltage Modulation: ≤2.5V;
- Under the balance load, the phase voltage shifting 120°±4°
- Distortion Factor: ≤ 0.05
- Wave Crest Factor: 1.31-1.51;
- Phase Voltage Adjustment Range in No Load: 115±12V
- Voltage Un-balance: 3V RMS Maximum
- Transient State Voltage Recover Time Conform to MIL-STD 704E Chart 4 standard, phase voltage transient state peak voltage range: 80 - 180 V, Steady voltage range 108 - 118 V.
- Inner wiring voltage drop compensate maximum 5% (adjustable).