Generator Set Specification | ||
Model | A-P220 | |
Max. Power | kVA | 220 |
kW | 176 | |
Rate Power | kVA | 200 |
kW | 160 | |
Frequency | Hz | 50 |
Rate Voltage | V | 400/230 |
Rate Current | A | 288.7 |
Fuel Tank Capacity | L | 300 |
Dimension For Open-type Genset | mm | 2550 X 800 X 1400 |
Weight For Open-type Genset | kg | 1630 |
Dimension For Soundproof Genset | mm | 3200 X 1080 X 1500 |
Weight For Soundproof Generator | kg | 2090 |
Noise Level for Soundproof Generator at 7M | dBA | 75 |
Battery for Starting | Two of 100A Free Maintenance Battery |
Engine Specification | ||
Engine Manufacturer | Perkins | |
Engine Brand | Perkins | |
Engine Model | 1106A-70TAG4 | |
No. of Cylinder | 6 Cylinder in line | |
Aspiration | Turbocharged and Air to Air Aftercooled | |
Governor | Electric | |
Engine Max. Output Power | kW | 196.3 |
Displacement | L | 7.0 |
Compression Ratio | 16.0 : 1 | |
Starting Voltage | V | 12 |
Bore | mm | 105 |
Stroke | mm | 135 |
Lubrication Oil Capacity | L | 16.5 |
Intake Air Flow | M3/Min | 9.4 |
Fuel Consumption at 100% Load | L/H | 45.8 |
Product Description
GENSET FEATURES
1. Cooperate with Leroy Somer, Marathon, Mecc Alte, Stamford for option
2. Optional manual and ATS control panels
3. Optional air filter, fuel filter, and oil filter
4. Comply with CE and ISO standards
5. All generator sets are gone through rigorous testing before being released to the marketplace, including 50% load, 75% load, 100% load, and all protection functions (over speed stop, high water temperature, low oil pressure, battery charging fail, emergency stop)
Alternator Specification | ||
Alternator Manufacturer | Cummins Generator Technologies | |
Alternator Model | UCI 274 H | |
Alternator Brand | Stamford | |
Rate Output | kVA | 200 |
Frequency | Hz | 50Hz |
Altitude | M | ≤1000 |
Insulation | Class H | |
Phase | 3 Phase | |
Working Temperature without power decrease | ≤40℃ | |
Working Altitude without power decrease | ≤1000m | |
Automatic Voltage Regulation | SX460 | |
Protection Grade | IP23 | |
Alternator for optional | Leroy Somer, Marathon, Mecc Alte and Hosem Brushless alternator for optional | |
Control Panel Specification | ||
Controller Brand | Deepsea | |
Controller Model | DSE7320 | |
Breaker Brand | Delixi | |
Breaker Capacity (A) | 400 | |
Battery Charger | Smartgen Model BAC06A | |
Emergency Stop Button | Supply | |
Automatic Mains Fail (AMF) | Supply | |
Fuel Level | Supply | |
Automatic Transfer Switch | ATS as optional part | |
The control panel supply the full protection with alarm and shutdown of the diesel generator include Start-up fault (generator set shutdown), High coolant temperature (alarm and generator set shutdown), Low oil pressure (alarm and generator set shutdown), Low fuel level (alarm), Low cooling fluid level alarm (as optional), Overload (alarm and generator set shutdown), Battery voltage high (alarm). | ||
Optional controller: Each model of Deepsea, Smartgen, ComAp brand controller. | ||
FAQ
Q1: Are you a factory or trade company?
A1: Factory. And we have our own trading company.
Q2: What is the exact address of your factory?
A2: Our company is located in C2 Building, Cangshan Wanda Plaza,
No. 216 Pushang Road, Fuzhou City, Fujian, China.
Q3: Warranty terms of your machine?
A3: One-year warranty for the machine.
Q4: Which payment term can you accept?
A4: 30% T/T With Order, 70% balance paid by T/T before shipment.